Dry-Type Transformers

HomeDry-Type Transformers2000kVA Cast-Resin Dry-Type Transformer (Large Capacity)

2000kVA Cast-Resin Dry-Type Transformer (Large Capacity)

The 2000 kva dry type transformer is a reliable and efficient power distribution solution widely used in commercial, industrial, and residential applications. Unlike oil-filled units, the 2000 kva dry type transformer uses air as the cooling medium, making it fire-resistant, environmentally friendly, and safe for indoor installation. It features low noise operation, minimal maintenance requirements, and excellent insulation performance. With high overload capacity and strong short-circuit resistance, the 2000 kva dry type transformer ensures stable voltage output and long service life, making it an ideal choice for modern electrical systems.

Core Parameters:

• Energy Efficiency: Tier 2 Efficiency (Complies with GB 20052-2024).

• Structure: Enhanced Resin Cast Insulation + Highly Efficient Forced Air Cooling.

• Warranty: 3-Year Standard Warranty (covers core components).


iconProduct Features

3-绿色环保.png

Safe & Eco-Friendly

Fully oil-free enhanced resin-cast operation. Inherently flame retardant and self-extinguishing, utterly eradicating explosion hazards in highly populated commercial and industrial areas.

5-低损耗.png

Low Loss & Long Life

Meets Tier 2 efficiency. Large-section copper windings drastically reduce resistance losses. The solid resin structure naturally resists moisture and dust, yielding a design lifespan of 25+ years.

4.png

High Reliability

Equipped with comprehensive smart protection including temp controllers and surge protection devices. The fully enclosed thick enclosure guarantees stability in complex indoor or semi-outdoor setups.

6-适应性强.png

Strong Adaptability

Modular design accommodates indoor floor installation or outdoor pre-installed layouts without building dedicated oil pits. Features a robust 1.2x short-term overload capacity for peak reliability.

14-维护.png

Low Maintenance Cost

No oil testing or replacement required for a 2000 kva dry type transformer. Regular dust wiping of cooling channels and visual checks on the winding insulation state are all that's needed, keeping O&M costs exceptionally low.

9-运维.png

Smart O&M (Optional)

A 2000 kva dry type transformer can be fitted with a smart monitoring system to remotely track winding temperatures, load currents, and insulation status, supporting fault warnings and minimizing manual patrols.


iconKey Specifications (2000kVA dry type transformer SCB13 Series)


ParameterTypical ValueDescription
Rated Capacity2000kVAMassive apparent power perfectly tailored for large industrial parks and commercial main branches.
Rated VoltageHV: 10kV | LV: 0.4kVStandard grid voltages, highly adaptable for varied regional distribution systems.
Vector GroupDyn11 / Yyn0Mainstream connections ensuring seamless integration and balanced load supply.
Impedance4.5% ~ 6.0%Effectively limits short-circuit currents, protecting downstream distribution equipment.
No-Load Loss≤ 2.05kW (SCB13)Tier 2 compliant; ultra-low idle consumption significantly reduces electricity overhead.
Load Loss (120℃)≤ 15.60kWCopper windings ensure minimal resistance, maximizing energy conversion under heavy load.
Winding Temp. Rise≤ 100K (Class F)Resin insulation and robust air convection prevent heat-induced insulation degradation.
Noise Level≤ 52~58dB(A)Shock-absorbing design creates an ultra-quiet footprint, avoiding noise pollution.
Cooling MethodAF (Forced Air Cooling)Highly efficient forced air cooling tailored for continuous large-capacity power distribution operations.


iconDetailed Description


The 2000kVA cast-resin dry-type transformer (mainstream SCB13 series) is a three-phase, Tier 2 efficiency unit recognized as a premier choice for large-capacity distribution. Its defining advantage is absolute environmental safety combined with a high-capacity load-bearing structure. Utilizing a solid epoxy resin cast, it blocks out moisture and dust while delivering unmatched flame-retardant properties—eliminating the severe fire and leakage risks associated with oil-immersed alternatives.


Engineered with large-section copper windings and an advanced forced air (AF) cooling system, this 2000 kva dry type transformer achieves highly stable, low-loss operation. Operating smoothly across -25℃ to 40℃, it exhibits exceptional overload capabilities. Because of its modular design and efficient cooling, it is widely deployed in highly sensitive and power-hungry zones such as large commercial complexes, vast data centers, and precision industrial main stations as a preferred dry type transformer.


iconSCB10 Type Parameters & Scenarios


ParameterTypical ValueDescription
Energy EfficiencyGB 20052-2024 Tier 2 (NX2)Adapts to basic energy-saving compliance requirements.
No-Load LossApprox. 2.20kWSlightly higher than SCB13, fulfilling fundamental large-voltage needs.
Load Loss (120℃)Approx. 16.50kWStable large-scale energy conversion under load.
Partial Discharge≤ 10pCReliable insulation performance, ensuring foundational operational safety.
Core MaterialStandard High-Grade Silicon SteelBalances magnetic permeability and cost for conventional operations.
Applicable ScenariosBudget-limited, load ≤ 60%Ideal for standard commercial blocks, small manufacturing hubs, and older grid upgrades.


iconStandard SCB13 Series Technical Reference


Capacity
(kVA)
Impedance
(%)
No-Load
Loss (W)
Load Loss
(W)
Total Weight
(kg)
Dimensions
W×D×H (mm)
8004.5980710023001400×1000×1400
10004.51150860027001450×1050×1450
12504.513501040032001550×1100×1550
16004.516501280038001650×1150×1650
20004.520501560045001750×1250×1800
25004.524501900053001850×1300×1900

* The table displays standard SCB13 dry-type technology platform parameters. Dimensions and weights are for reference and may vary based on specific enclosure customizations.


iconFAQ


Installing a 2000kVA dry-type transformer requires focusing on large-scale structural handling, extensive layout adaptation, and highly efficient ventilation. Core precautions include:

1) Installation Layout Adaptation: Maintain a safe distance of ≥1.5m from surrounding electrical equipment and cables. Reserve a broader maintenance channel of ≥1.2m to ensure safe operational space for this large footprint.

2) Cooling Space Reservation: Ensure a clearance of ≥1.5m above the unit and ≥1.0m around the sides. Do not install in completely sealed spaces. Natural airflow must be unobstructed. Given its reliance on AF (forced air) cooling, the room must be equipped with adequate ventilation ducts for optimal heat exhaust.

3) Power Match & Grounding: Ensure the input/output voltages strictly match the 10kV grid. The enclosure and core must be reliably grounded with a resistance of ≤4Ω to provide uncompromised leakage protection.

4) Handling & Flexible Mounting: This unit is very heavy (approx. 4500kg). It must be handled strictly using dedicated heavy-duty lifting gear, ensuring no bumps occur to the resin windings. For floor installation, the ground must be flat and solid, utilizing robust standard brackets. Tilting can impair both insulation and cooling performance.

Please Contact Us!
Stay Current on Transformers!
Discover the latest in transformer technology, industry trends, and innovations – all in one click. Each month, you’ll receive updates on our newest products, engineering solutions, exhibitions, and real-world applications from our global customers.
WHAT ARE YOU LOOKING FOR?
*
This field is required
Total quantity you need
*
This field is required
*
This field is required
Email format error
Due to email instability, you might miss our correspondence. Please provide your phone number for alternative contact.
This field is required
Telephone information is wrong!
Send Message
Contact

Whatsapp: +86-13961294414

ADD: No. 1, Yulong Middle Road, Xuejia Town, Xinbei District, Changzhou City, China

Mobile: 0086-15380068868

bottom_media_icon1
Quick Links

Home

Products

Industry Solutions

About Us

Resources

Contact Us

Products

Oil-Immersed Transformers

Dry-Type Transformers

New Energy & Compact Substation

Specialty Transformers

Other Related

Customization Capabilities

Manufacturing & Quality