The 1600 kva dry type transformer is a highly reliable and energy-efficient power distribution solution, widely adopted in commercial and industrial applications. Unlike conventional oil-immersed units, this 1600 kva dry type transformer utilizes air-cooled insulation, completely removing fire hazards and greatly reducing ongoing maintenance needs. Engineered with Class H insulation, it delivers outstanding thermal stability and ultra-low noise operation, making it perfectly suited for sensitive indoor environments. Its compact design, excellent overload capacity, and eco-friendly construction make the 1600 kva dry type transformer the preferred choice for hospitals, data centers, office buildings, and any facility requiring safe, dependable power delivery with minimal environmental impact and extended long-term service life.
Core Parameters:
• Energy Efficiency: Tier 2 Efficiency (Complies with GB 20052-2024).
• Structure: Enhanced Resin Cast Insulation + Highly Efficient Forced Air Cooling.
• Warranty: 3-Year Standard Warranty (covers core components).
Product Features

Fully oil-free enhanced resin-cast operation. Inherently flame retardant and self-extinguishing, utterly eradicating explosion hazards in highly populated commercial and industrial areas.

Meets Tier 2 efficiency. Large-section copper windings drastically reduce resistance losses. The solid resin structure naturally resists moisture and dust, yielding a design lifespan of 25+ years.

Equipped with comprehensive smart protection including temp controllers and surge protection devices. The fully enclosed thick enclosure of the 1600 kva dry type transformer guarantees stability in complex indoor or semi-outdoor setups.

Modular design of the 1600 kva dry type transformer accommodates indoor floor installation or outdoor pre-installed layouts without building dedicated oil pits. Features a robust 1.2x short-term overload capacity for peak reliability.

No oil testing or replacement required. Regular dust wiping of cooling channels and visual checks on the winding insulation state are all that's needed, keeping O&M costs exceptionally low.

Can be fitted with a smart monitoring system to remotely track winding temperatures, load currents, and insulation status, supporting fault warnings and minimizing manual patrols.
Key Specifications (1600kVA dry type transformer SCB13 Series)
| Parameter | Typical Value | Description |
| Rated Capacity | 1600kVA | Massive apparent power perfectly tailored for large industrial parks and commercial main branches. |
| Rated Voltage | HV: 10kV | LV: 0.4kV | Standard grid voltages, highly adaptable for varied regional distribution systems. |
| Vector Group | Dyn11 / Yyn0 | Mainstream connections ensuring seamless integration and balanced load supply. |
| Impedance | 4.5% ~ 6.0% | Effectively limits short-circuit currents, protecting downstream distribution equipment. |
| No-Load Loss | ≤ 1.65kW (SCB13) | Tier 2 compliant; ultra-low idle consumption significantly reduces electricity overhead. |
| Load Loss (120℃) | ≤ 12.80kW | Copper windings ensure minimal resistance, maximizing energy conversion under heavy load. |
| Winding Temp. Rise | ≤ 100K (Class F) | Resin insulation and robust air convection prevent heat-induced insulation degradation. |
| Noise Level | ≤ 52~58dB(A) | Shock-absorbing design creates an ultra-quiet footprint, avoiding noise pollution. |
| Cooling Method | AF (Forced Air Cooling) | Highly efficient forced air cooling tailored for continuous large-capacity power distribution operations. |
Detailed Description
The 1600kVA cast-resin dry-type transformer (mainstream SCB13 series) is a three-phase, Tier 2 efficiency unit recognized as a premier choice for large-capacity distribution. Its defining advantage is absolute environmental safety combined with a high-capacity load-bearing structure. Utilizing a solid epoxy resin cast, it blocks out moisture and dust while delivering unmatched flame-retardant properties—eliminating the severe fire and leakage risks associated with oil-immersed alternatives.
Engineered with large-section copper windings and an advanced forced air (AF) cooling system, the 1600 kva dry type transformer achieves highly stable, low-loss operation. This reliable dry type transformer operates smoothly across -25℃ to 40℃ and exhibits exceptional overload capabilities. Because of its modular design and efficient cooling, it is widely deployed in highly sensitive and power-hungry zones such as large commercial complexes, vast data centers, and precision industrial main stations.
SCB10 Type Parameters & Scenarios
| Parameter | Typical Value | Description |
| Energy Efficiency | GB 20052-2024 Tier 2 (NX2) | Adapts to basic energy-saving compliance requirements. |
| No-Load Loss | Approx. 1.80kW | Slightly higher than SCB13, fulfilling fundamental large-voltage needs. |
| Load Loss (120℃) | Approx. 13.50kW | Stable large-scale energy conversion under load. |
| Partial Discharge | ≤ 10pC | Reliable insulation performance, ensuring foundational operational safety. |
| Core Material | Standard High-Grade Silicon Steel | Balances magnetic permeability and cost for conventional operations. |
| Applicable Scenarios | Budget-limited, load ≤ 60% | Ideal for standard commercial blocks, small manufacturing hubs, and older grid upgrades. |
Standard SCB13 Series Technical Reference
| Capacity (kVA) | Impedance (%) | No-Load Loss (W) | Load Loss (W) | Total Weight (kg) | Dimensions W×D×H (mm) |
| 630 | 4.5 | 810 | 5880 | 1950 | 1350×1000×1350 |
| 800 | 4.5 | 980 | 7100 | 2300 | 1400×1000×1400 |
| 1000 | 4.5 | 1150 | 8600 | 2700 | 1450×1050×1450 |
| 1250 | 4.5 | 1350 | 10400 | 3200 | 1550×1100×1550 |
| 1600 | 4.5 | 1650 | 12800 | 3800 | 1650×1150×1650 |
| 2000 | 4.5 | 2050 | 15600 | 4500 | 1750×1250×1800 |
* The table displays standard SCB13 dry-type technology platform parameters. Dimensions and weights are for reference and may vary based on specific enclosure customizations.
FAQ
Installing a 1600kVA dry-type transformer requires focusing on large-scale structural handling, extensive layout adaptation, and highly efficient ventilation. Core precautions include:
1) Installation Layout Adaptation: Maintain a safe distance of ≥1.5m from surrounding electrical equipment and cables. Reserve a broader maintenance channel of ≥1.2m to ensure safe operational space for this large footprint.
2) Cooling Space Reservation: Ensure a clearance of ≥1.5m above the unit and ≥1.0m around the sides. Do not install in completely sealed spaces. Natural airflow must be unobstructed. Given its reliance on AF (forced air) cooling, the room must be equipped with adequate ventilation ducts for optimal heat exhaust.
3) Power Match & Grounding: Ensure the input/output voltages strictly match the 10kV grid. The enclosure and core must be reliably grounded with a resistance of ≤4Ω to provide uncompromised leakage protection.
4) Handling & Flexible Mounting: This unit is very heavy (approx. 3800kg). It must be handled strictly using dedicated heavy-duty lifting gear, ensuring no bumps occur to the resin windings. For floor installation, the ground must be flat and solid, utilizing robust standard brackets. Tilting can impair both insulation and cooling performance.